EPA 608 practice questions, with worked answers
Here are 21 original EPA 608-style questions across the four sections of the Section 608 exam, Core, Type I, Type II and Type III, with the answer and the rule from 40 CFR 82 subpart F under each. Try each one before you open the answer; the trap under it is the mistake most people make.
- 21
- practice questions
- 4
- sections covered
- 0
- of them in any mock
- Free
- no sign-up
Last checked · Original questions written for LifeScore from 40 CFR 82 subpart F, not exam items
By the LifeScore Editorial Team · Updated · How we check facts · How this is scored
What do EPA 608 Core questions look like?
Ozone depletion and climate, the Clean Air Act and Montreal Protocol, the venting prohibition, refrigerant classes, recovery, recycling and reclaiming, the three Rs, dehydration, safety, shipping and cylinders, and pressure and temperature. The first question is worked in full; the rest open when you tap. The [Core page](/epa-608-core-practice-test) has a free 12-question drill.
EPA 608-style question 1 · Cylinders
To what level may a recovery cylinder be filled with liquid refrigerant?
- A100% of its capacity
- B50% of its capacity
- CNo more than 80% of its capacity
- D95% of its capacity
Worked answer
C: No more than 80% of its capacity. The 20% of space left lets the liquid expand as the temperature rises without hydrostatic pressure building up and rupturing the cylinder.
The trap: Filling to 100%. Liquid refrigerant expands as it warms, and a full cylinder can rupture.
EPA 608-style question 2 · Cylinders
A refillable recovery cylinder is stamped with a hydrostatic test date of September 2023. When is its next retest due?
- ASeptember 2033
- BSeptember 2026
- CSeptember 2024
- DSeptember 2028
Show the answer
D: September 2028. Refillable DOT recovery cylinders must be retested every 5 years: September 2023 + 5 years = September 2028. Do not fill a cylinder that is out of date.
EPA 608-style question 3 · Safety
Which ASHRAE Standard 34 safety group is R-32 in?
- AA3: lower toxicity, higher flammability
- BA1: lower toxicity, no flame propagation
- CA2L: lower toxicity, lower flammability
- DB1: higher toxicity, no flame propagation
Show the answer
C: A2L: lower toxicity, lower flammability. R-32 is in group A2L. The letter is toxicity (A lower, B higher); the number is flammability (1 no flame propagation, 2L lower flammability, 3 higher flammability).
EPA 608-style question 4 · Pressure
A recovery cylinder's gauge reads 85 psig. About what is the absolute pressure inside it?
- A99.7 psia
- B70.3 psia
- C85 psia
- D14.7 psia
Show the worked answer
A: 99.7 psia. A gauge reads pressure above the atmosphere. Absolute pressure adds atmospheric pressure at sea level: 85 + 14.7 = 99.7 psia.
- psia = psig + 14.7.
- 85 + 14.7 = 99.7.
- So about 99.7 psia.
The trap: Subtracting 14.7 (70.3). That converts the wrong way.
EPA 608-style question 5 · Recovery
What is the difference between recycling and reclaiming refrigerant?
- ARecycling cleans refrigerant for reuse, often on site; reclaiming reprocesses it to new-product purity, verified by chemical analysis
- BThey mean the same thing
- CRecycling is done only at a reclamation plant
- DReclaiming means removing refrigerant into a cylinder without testing it
Show the worked answer
A: Recycling cleans refrigerant for reuse, often on site; reclaiming reprocesses it to new-product purity, verified by chemical analysis. Recovering is removing refrigerant into a container. Recycling cleans it (oil separation, filter-driers) for reuse, often in the same shop. Reclaiming reprocesses it to the purity of new refrigerant, confirmed by chemical analysis, usually at a certified reclaimer.
- Recover: take it out and store it.
- Recycle: clean it for reuse.
- Reclaim: reprocess it to new-product purity and test it.
The trap: Treating "recover" and "reclaim" as the same. Recovery is only the removal.
What do EPA 608 Type I questions look like?
What counts as a small appliance, recovery requirements (80% or 90%, or 4 inches of mercury vacuum), self-contained and system-dependent recovery, piercing valves, and safety. The first question is worked in full; the rest open when you tap. The [Type I page](/epa-608-type-1-practice-test) has a free 12-question drill.
EPA 608-style question 6 · Small appliances
Under the Section 608 rules, a small appliance is one that is manufactured, charged and hermetically sealed in a factory with
- A5 pounds or less of refrigerant
- B50 pounds or less of refrigerant
- C1 pound or less of refrigerant
- D15 pounds or less of refrigerant
Worked answer
A: 5 pounds or less of refrigerant. A small appliance is fully manufactured, charged and hermetically sealed in a factory with five pounds or less of refrigerant.
The trap: Using 15 or 50 pounds, the leak repair and other thresholds. A small appliance is 5 pounds or less.
EPA 608-style question 7 · Cylinders
A recovery cylinder is rated to hold 30 pounds of refrigerant. What is the most refrigerant you should put in it?
- A21 pounds
- B30 pounds
- C15 pounds
- D24 pounds
Show the answer
D: 24 pounds. Fill a recovery cylinder to no more than 80% of its capacity: 30 × 0.8 = 24 pounds. The space left lets the liquid expand safely.
EPA 608-style question 8 · Small appliances
A drinking-water cooler was manufactured, charged and hermetically sealed at the factory with 6 pounds of refrigerant. Is it a small appliance under Section 608?
- AYes; anything under 15 pounds is a small appliance
- BNo; it holds more than 5 pounds
- CYes; it is a small appliance (Type I)
- DNo; small appliances must use R-12
Show the answer
B: No; it holds more than 5 pounds. A small appliance is manufactured, charged and hermetically sealed in a factory with 5 pounds or less. This one was factory sealed with 6 pounds, so it is not, because the charge is over 5 pounds.
EPA 608-style question 9 · Refrigerants
A small appliance's nameplate lists R-290. What type of refrigerant is it?
- AHFC (hydrofluorocarbon)
- BHCFC (hydrochlorofluorocarbon)
- CCFC (chlorofluorocarbon)
- DHC (hydrocarbon)
Show the answer
D: HC (hydrocarbon). R-290 is propane: a hydrocarbon, which is highly flammable. Knowing the type tells you which recovery cylinder and precautions to use.
EPA 608-style question 10 · Recovery
A technician recovers refrigerant from a household refrigerator whose compressor does not run, using recovery equipment manufactured in 2015. What must be recovered?
- A80% of the refrigerant, or a 4-inch Hg vacuum
- B90% of the refrigerant, or a 4-inch Hg vacuum
- C100% of the refrigerant
- D50% of the refrigerant
Show the worked answer
A: 80% of the refrigerant, or a 4-inch Hg vacuum. For small appliances, equipment made after November 15, 1993 must recover 90% when the compressor works and 80% when it does not, or achieve a 4-inch Hg vacuum. This compressor does not run, so 80%.
- Equipment date: 2015, after November 15, 1993.
- Compressor: not running.
- Rule: 80%, or a 4-inch Hg vacuum.
The trap: Using 90%. That figure is for a working compressor.
EPA 608-style question 11 · Small appliances
A dehumidifier holds 9 ounces of R-410A. How many pounds is that?
- A0.5625 pound
- B0.9 pound
- C1.44 pounds
- D0.09 pound
Show the worked answer
A: 0.5625 pound. There are 16 ounces in a pound: 9 ÷ 16 = 0.5625 pound, well under the 5-pound small appliance limit.
- 16 ounces = 1 pound.
- 9 ÷ 16 = 0.5625.
- So 0.5625 pound.
The trap: Dividing by 10 (0.9 pound). Ounces and pounds are not decimal.
What do EPA 608 Type II questions look like?
Leak detection, leak rate thresholds and repair deadlines, required evacuation levels, recovery techniques, superheat and subcooling, charging, and refrigeration safety. The first question is worked in full; the rest open when you tap. The [Type II page](/epa-608-type-2-practice-test) has a free 12-question drill.
EPA 608-style question 12 · Leak repair
What is the leak rate threshold for comfort cooling appliances with 50 pounds or more of ozone-depleting refrigerant?
- A30% per year
- B35% per year
- C10% per year
- D20% per year
Worked answer
C: 10% per year. Since January 1, 2019, the thresholds are 10% for comfort cooling, 20% for commercial refrigeration and 30% for industrial process refrigeration.
The trap: Swapping the thresholds. Comfort cooling is the strictest at 10%; commercial refrigeration is 20% and industrial process 30%.
EPA 608-style question 13 · Superheat and subcooling
The head pressure corresponds to a condensing (saturation) temperature of 125°F, and the liquid line at the condenser outlet measures 122°F. What is the subcooling?
- A3°F
- B125°F
- C13°F
- D247°F
Show the answer
A: 3°F. Subcooling = saturation temperature − measured liquid line temperature = 125 − 122 = 3°F.
EPA 608-style question 14 · Equipment types
How does EPA classify R-500, and which certification covers a field-built (not small-appliance) system that uses it?
- AA low-pressure refrigerant; a field-built system using it needs Type III
- BA medium-pressure refrigerant; a field-built system using it needs Type III
- CA high-pressure refrigerant; a field-built system using it needs Type II
- DA medium-pressure refrigerant; a field-built system using it needs Type II
Show the answer
D: A medium-pressure refrigerant; a field-built system using it needs Type II. By its saturation pressure at 104°F, R-500 is medium-pressure (low below 45 psia, medium 45 to 170, high 170 to 355, very high above 355). Low-pressure equipment is Type III; medium-, high- and very high-pressure equipment is Type II.
EPA 608-style question 15 · Evacuation levels
Before a major repair, a technician recovers refrigerant from an appliance holding 250 pounds of R-134a, using recovery equipment made in 2010. To what level must the appliance be evacuated?
- A15 inches of mercury vacuum
- B10 inches of mercury vacuum
- C4 inches of mercury vacuum
- D0 inches of mercury vacuum
Show the worked answer
A: 15 inches of mercury vacuum. R-134a is a medium-pressure refrigerant. For a medium-pressure appliance with 200 pounds or more, recovered with equipment made on or after November 15, 1993, table 1 of 40 CFR 82.156 requires 15 inches of mercury vacuum.
- R-134a: medium pressure.
- Charge: 250 lb, so 200 pounds or more.
- Equipment after November 15, 1993: 15 inches.
The trap: Using 10 inches, the figure for under 200 pounds.
EPA 608-style question 16 · Superheat and subcooling
The liquid line leaving the condenser measures 98°F, and the head pressure corresponds to a condensing temperature of 112°F. What is the subcooling?
- A14°F
- B210°F
- C98°F
- D7°F
Show the worked answer
A: 14°F. Subcooling is how far the liquid has been cooled below its condensing (saturation) temperature: 112 − 98 = 14°F.
- Subcooling = saturation temperature − liquid line temperature.
- 112 − 98 = 14.
- So 14°F of subcooling.
The trap: Subtracting the other way round, or confusing it with superheat, which is measured on the suction side.
EPA 608-style question 17 · Leak repair
A commercial refrigeration appliance holding 120 pounds of an ozone-depleting refrigerant needs 30 pounds added to restore a full charge, 6 months after it was last charged. What is the leak rate, and must it be repaired?
- A50% per year; yes, it is over the 20% threshold
- B25% per year; yes, it is over the 20% threshold
- C25% per year; no, it is under the 35% threshold
- D12.5% per year; no
Show the worked answer
A: 50% per year; yes, it is over the 20% threshold. Using the annualizing method: (pounds added ÷ full charge) × (365 ÷ days since the last charge) × 100 = (30 ÷ 120) × (365 ÷ about 182) × 100 ≈ 50% per year. Commercial refrigeration with 50 pounds or more must be repaired above 20%.
- Share of the charge: 30 ÷ 120 = 25% in about half a year.
- Projected over a year: about 50%.
- Commercial refrigeration threshold: 20%. 50% is over, so repair.
The trap: Forgetting to project to a full year (25%). The leak rate is per year.
More questions like these
Eight full EPA 608-style mocks and 16 drills, every answer explained like the ones on this page.
The EPA 608 Pass Pack gives you 8 full mocks on the real clock, 16 drills of 12 questions for the sections that cost you points, and a predictor that turns your mocks into the odds of reaching your target. One payment, no subscription, and your free score stays free.
Prep courses for these tests usually cost $19 to $129. The EPA 608 Pass Pack is US$39 (£29), once.
- 8
- timed mocks
- 16
- topic drills
- 1
- score predictor
What do EPA 608 Type III questions look like?
Leak testing at no more than 10 psig, purge units, rupture discs, recovery to 25 mm Hg absolute, water in the tubes during recovery, charging and safety. The first question is worked in full; the rest open when you tap. The [Type III page](/epa-608-type-3-practice-test) has a free 12-question drill.
EPA 608-style question 18 · Rupture disc
The rupture disc on the evaporator of a low-pressure chiller is set to burst at
- A150 psig
- B300 psig
- C15 psig
- D5 psig
Worked answer
C: 15 psig. Low-pressure chillers are not built for high pressure. The rupture disc opens at 15 psig to protect the vessel.
The trap: Choosing a high-pressure figure. Low-pressure chillers are built for low pressures, so the disc opens at 15 psig.
EPA 608-style question 19 · Pressure
An evaporator gauge reads 4 inches of mercury vacuum. Using 1 inch of mercury ≈ 0.491 psi and 14.7 psia for atmospheric pressure, about what is the absolute pressure?
- AAbout 13.5 psia
- BAbout 16.7 psia
- CAbout 2.0 psia
- DAbout 12.7 psia
Show the answer
D: About 12.7 psia. 4 in Hg × 0.491 = 1.96 psi below atmospheric. 14.7 − 1.96 ≈ 12.7 psia.
EPA 608-style question 20 · Leak testing
A technician wants to leak test a low-pressure centrifugal chiller by raising its pressure. What is the most the pressure should be raised to?
- A10 psig
- B15 psig
- C50 psig
- D150 psig
Show the worked answer
A: 10 psig. The rupture disc on a low-pressure chiller opens at 15 psig, so leak testing raises the pressure to no more than 10 psig, usually with controlled hot water or heating blankets (or a pressurizing kit).
- Rupture disc setting: 15 psig.
- Stay below it with a margin.
- So no more than 10 psig.
The trap: Choosing 15 psig. That is where the disc bursts, not a safe test pressure.
EPA 608-style question 21 · Recovery
Why should liquid refrigerant be recovered first from a low-pressure chiller?
- AIt removes most of the charge quickly before vapor recovery
- BVapor recovery damages the purge unit
- CLiquid refrigerant cannot be recovered after the vapor
- DIt raises the pressure for a leak test
Show the worked answer
A: It removes most of the charge quickly before vapor recovery. Most of a chiller's charge is liquid, and liquid moves far faster than vapor. Recovering liquid first, then vapor down to the required level, saves hours, and water is kept circulating in the tubes to stop them freezing as the pressure drops.
- Most of the charge is liquid.
- Liquid transfers much faster than vapor.
- So recover liquid first, then vapor.
The trap: Thinking the order is about safety of the purge unit. It is about speed.
Which table do these EPA 608 questions keep coming back to?
The required evacuation levels. If you can read a row from the refrigerant, the charge and the recovery equipment date, most Type II and Type III questions with numbers become quick points.
| Appliance | Equipment before Nov 15, 1993 | On or after Nov 15, 1993 |
|---|---|---|
| HCFC-22 appliance, under 200 lb | 0 | 0 |
| HCFC-22 appliance, 200 lb or more | 4 | 10 |
| Very high-pressure appliance | 0 | 0 |
| Other high-pressure appliance, under 200 lb | 4 | 10 |
| Other high-pressure appliance, 200 lb or more | 4 | 15 |
| Medium-pressure appliance, under 200 lb | 4 | 10 |
| Medium-pressure appliance, 200 lb or more | 4 | 15 |
| Low-pressure appliance | 25 (inches of mercury vacuum) | 25 mm Hg absolute |
Notice how many wrong options above are a real number from the next row: 10 where 200 pounds or more needs 15, 0 where only HCFC-22 gets 0. That is how the real exam is built too, so learn the row with its conditions.
How should I use EPA 608 practice questions?
Answer each before you open the working, write down the rule behind every miss, and then take a full timed practice test to check the rules have stuck.
A sample set is small, so a good score here proves little. A wrong answer, though, points straight at a rule you can learn in a minute. Write each one on a card.
Then take the free EPA 608 practice test, which has 100 questions across all four sections, scored against 18 of 25 each. How to pass the EPA 608 turns the result into a seven-day plan.
Are these like the real EPA 608 exam questions?
They follow the rules the exam tests in the same four-option style, but they are original and none is a real exam question.
Certifying organizations write their tests from an EPA-approved bank that is not public, and copies online are often out of date, especially on leak repair rules that changed in 2016 and later. Every question here was written for LifeScore and checked by an independent re-solve that saw only the question and the options. The EPA 608 certification guide explains how the real exam is given.
Frequently asked questions
Are these real EPA 608 exam questions?
Where can I read the rules?
Do these questions appear in your mocks?
How many questions are on the real exam?
Ready for a full test?
Eight full EPA 608-style mocks, 16 drills and every answer explained, for one payment.
The EPA 608 Pass Pack gives you 8 full mocks on the real clock, 16 drills of 12 questions for the sections that cost you points, and a predictor that turns your mocks into the odds of reaching your target. One payment, no subscription, and your free score stays free.
Prep courses for these tests usually cost $19 to $129. The EPA 608 Pass Pack is US$39 (£29), once.
- 8
- timed mocks
- 16
- topic drills
- 1
- score predictor